Electrical power systems require reliable protection to detect faults and isolate only the affected section of the network. A properly designed protection system helps protect transformers, motors, generators, cables, switchgear, and other electrical equipment from damage caused by short circuits and abnormal operating conditions. A Relay Protection Coordination Study is an important part of electrical system protection. It determines the appropriate protection settings so that protective devices operate in a coordinated sequence. ETAP is widely used by electrical engineers to model power systems, perform fault calculations, develop time-current characteristic curves, and verify protection coordination.
This guide explains the major steps involved in carrying out a Relay Protection Coordination Study using ETAP, from creating the electrical model to reviewing relay settings and coordination curves.
What Is a Relay Protection Coordination Study?
A Relay Protection Coordination Study evaluates the operation of protective relays, circuit breakers, fuses, and other protection devices under different fault conditions. The primary objective is to ensure that the protective device closest to the fault operates first while upstream devices remain available as backup protection. For example, if a fault occurs on a downstream feeder, the feeder relay should normally trip before the upstream incomer relay. This selective operation helps minimize the portion of the electrical network that is disconnected.
A properly executed Relay Protection Coordination Study considers short-circuit levels, equipment ratings, relay characteristics, time delays, pickup currents, and coordination intervals.
Why Use ETAP for Relay Protection Coordination?

Manual coordination of multiple protection devices can become complex, particularly in large industrial facilities containing several voltage levels and interconnected sources. ETAP provides an integrated environment for modeling electrical networks and analyzing protection performance. Engineers can create a single-line diagram and use the model for load flow, short-circuit, motor starting, arc flash, and protection studies.
For a Relay Protection Coordination Study, ETAP can generate time-current characteristic curves and allow engineers to compare the operating characteristics of multiple protective devices.
Step 1: Develop the Electrical System Model
The first step is to create an accurate electrical network model in ETAP. The model typically includes utility sources, generators, transformers, motors, switchboards, MCCs, cables, feeders, circuit breakers, and protective relays. Equipment ratings and electrical parameters should be entered based on approved project documents and manufacturer data.
Important information may include:
- Transformer MVA and impedance
- Generator ratings
- Cable size and length
- Motor ratings
- Breaker ratings
- CT ratios
- Relay characteristics
- Utility short-circuit information
- System voltage levels
The accuracy of the model directly affects the reliability of the study results.
Step 2: Perform Load Flow Analysis
Before configuring protection settings, engineers should understand the normal operating conditions of the electrical system. Load flow analysis provides information such as bus voltages, power flow, transformer loading, and feeder currents. These values help establish the normal operating current of equipment and assist in selecting appropriate relay pickup settings. The results should be reviewed for overloaded equipment, abnormal voltage levels, and unusual current flows before proceeding with protection coordination.
Step 3: Perform Short-Circuit Analysis
Short-circuit analysis is a fundamental input to a Relay Protection Coordination Study. The engineer determines the prospective fault current at important buses and equipment locations.
Typical fault types include:
- Three-phase faults
- Line-to-line faults
- Line-to-ground faults
- Double-line-to-ground faults
The calculated fault currents are then used to verify whether protective devices can detect and interrupt the expected fault conditions. Short-circuit results are also important for checking circuit-breaker interrupting ratings and determining relay operating points.
Step 4: Select Protective Device Characteristics
The next step is to define the protective devices and their operating characteristics.
Depending on the application, engineers may configure:
- Instantaneous overcurrent protection
- Time-overcurrent protection
- Long-time protection
- Short-time protection
- Ground-fault protection
- Undervoltage or overvoltage protection
- Other specialized protection functions
In ETAP, the engineer can select appropriate relay models and protection curves and enter relevant settings such as pickup current, time dial, and instantaneous pickup. The selected settings should reflect the equipment requirements, operating philosophy, and applicable project standards.
Step 5: Generate Time-Current Characteristic Curves
One of the most useful features of ETAP for a Relay Protection Coordination Study is the ability to generate time-current characteristic curves. These curves show the relationship between fault current and operating time for different protective devices. Engineers can place downstream and upstream relays on the same graph to determine whether sufficient separation exists between their operating characteristics. The objective is to achieve selectivity while maintaining adequate protection for the equipment.
Step 6: Coordinate Downstream and Upstream Devices
Protection coordination is generally performed from the downstream devices toward the upstream source. Suppose a motor feeder is protected by a downstream relay and an upstream switchboard feeder relay. For a fault on the motor feeder, the downstream relay should operate first. The upstream relay should operate only if the downstream protection fails. The engineer adjusts relay pickup and time settings to achieve the required coordination margin. During the Relay Protection Coordination Study, engineers should also consider motor starting current, transformer inrush, cable damage curves, transformer damage curves, and equipment withstand capabilities.
Step 7: Check Coordination for Different Fault Conditions
Coordination should not be verified at only one fault current. Engineers should examine different operating conditions and fault locations.
The study may include:
- Minimum fault current
- Maximum fault current
- Phase faults
- Ground faults
- Utility-connected operation
- Generator-connected operation
- Different transformer configurations
- Normal and alternate operating conditions
This ensures that protection settings remain effective across the expected system operating scenarios.
Step 8: Review Relay Settings and Protection Margins
After generating the coordination curves, engineers review the proposed settings in detail.
The review should consider:
- Relay pickup current
- Time multiplier or time dial
- Instantaneous settings
- Ground-fault settings
- Coordination time interval
- Equipment damage curves
- Cable withstand characteristics
- Breaker operating time
- CT performance
The final settings should provide adequate sensitivity without causing unnecessary nuisance trips.
Step 9: Preparing the Relay Protection Coordination Study Report
The final stage of a Relay Protection Coordination Study is documentation. A typical report includes the electrical system description, study assumptions, short-circuit results, protective device data, relay settings, coordination curves, equipment ratings, and recommendations. The report should clearly identify any coordination issues and document the final recommended settings.
Common Challenges in Relay Protection Coordination Study

Several practical challenges can affect a Relay Protection Coordination Study. These include incomplete equipment data, inaccurate CT information, changes in the electrical network, multiple power sources, motor starting currents, and limited coordination margins. Another challenge is balancing selectivity with fast fault clearance. Excessive time delays can improve coordination but may increase equipment exposure to fault energy.
Engineers therefore need to evaluate protection performance together with equipment limitations and the overall electrical protection philosophy.
Benefits of Using ETAP for Relay Protection Coordination Study
Using ETAP can simplify the analysis of complex electrical networks by integrating system modeling, fault calculations, and protection analysis in one environment.
For engineers, this approach can provide:
- Improved visualization of protection characteristics
- Faster evaluation of relay settings
- Easier comparison of multiple scenarios
- Better documentation of protection settings
- Identification of coordination conflicts
- Integration with other electrical system studies
A structured Relay Protection Coordination Study using ETAP can therefore support safer and more reliable electrical system design.
Conclusion
A well-executed Relay Protection Coordination Study is essential for developing a reliable electrical protection system. By accurately modeling the network, performing load flow and short-circuit analysis, selecting suitable relay characteristics, and reviewing time-current curves, engineers can develop coordinated protection settings. ETAP provides a practical platform for carrying out these analyses and evaluating protection performance under different operating conditions. When combined with accurate project data and sound engineering judgment, the software can help electrical engineers identify coordination issues and develop well-documented protection settings for industrial power systems.
Take your electrical engineering skills to the next level with Stepin Engineering’s Advanced Electrical Design Engineering course, featuring practical training in ETAP, protection coordination, short-circuit analysis, load flow, arc flash, and other essential electrical design studies – join the course and build industry-ready expertise.
Frequently Asked Questions
1. What is the main purpose of a Relay Protection Coordination Study?
The main purpose is to ensure that protective devices operate selectively. The device closest to the fault should normally clear the fault first, while upstream devices provide backup protection.
2. Why is ETAP used for Relay Protection Coordination Study?
ETAP allows engineers to model electrical networks, calculate fault currents, configure protective devices, generate time-current curves, and evaluate coordination between multiple protection devices.
3. What information is required for a Relay Protection Coordination Study?
Typical requirements include single-line diagrams, equipment ratings, transformer impedances, cable data, motor information, utility fault levels, CT ratios, breaker information, and existing relay settings.
4. What are time-current characteristic curves?
Time-current characteristic curves show how quickly a protective device operates at different current levels. Comparing curves helps engineers determine whether downstream and upstream devices are properly coordinated.
5. Can ETAP be used for other electrical studies?
Yes. ETAP can support several electrical engineering studies, including load flow, short-circuit analysis, arc flash analysis, motor starting, transient stability, and protection coordination.